1. Discharge Depth
The discharge depth refers to the degree to which the discharge stops during use. 100% depth means that the entire capacity is discharged. The life of lead-acid batteries is greatly affected by the depth of discharge. The key design considerations are deep cycle use, shallow cycle use, or floating charge use. If a shallow cycle battery is used for deep cycle use, the lead-acid battery will fail quickly.
Because the positive active material lead dioxide itself is not firmly bonded to each other, lead sulfate is generated during discharge and restored to lead dioxide during charging. The molar volume of lead sulfate is larger than that of lead oxide, so the volume of the active material expands during discharge. If one mole of lead oxide is converted into one mole of lead sulfate, the volume increases by 95%. Such repeated contraction and expansion gradually loosens the mutual bond between lead dioxide particles and makes them easy to fall off. If only 20% of the active material of one mole of lead dioxide is discharged, the degree of contraction and expansion is greatly reduced, and the bond force is slowly destroyed. Therefore, the deeper the discharge depth, the shorter its cycle life.
2. Overcharge degree
A large amount of gas is precipitated during overcharge, and the active material of the positive plate is impacted by the gas, which promotes the shedding of the active material; in addition, the positive grid alloy is also severely corroded by anodic oxidation, so the battery overcharge will shorten its application period.
3. Effect of temperature
The life of lead-acid batteries increases with increasing temperature. Between 10℃~35℃, each 1℃ increase can increase the life by about 5~6 cycles. Between 35℃~45℃, each 1℃ increase can extend the life by more than 25 cycles. Above 50℃, the life is reduced due to the loss of negative electrode sulfide capacity.
The battery life increases with increasing temperature within a certain temperature range because the capacity increases with increasing temperature. If the discharge capacity remains unchanged, the depth of discharge decreases when the temperature rises, and the solid life is extended.
4. Effect of sulfuric acid concentration
Although the increase in acid density is beneficial to the capacity of the positive plate, the self-discharge of the battery increases, the corrosion of the grid is also accelerated, and the loosening and shedding of lead dioxide is also promoted. As the density of acid used in the battery increases, the cycle life decreases.
5. Influence of discharge current density
As the discharge current density increases, the battery life decreases because the positive lead dioxide loosens and falls off under high current density and high acid concentration conditions.
Lead-acid battery life
Oct 26, 2024